Specification
AH-0014 Flame Detector
Model | AH-0014 | ||
Type | 2 wire | 3 wire | 4 wire |
Alarm Contact | N/A | N/A | 0.8A @30V DC, 0.4A @125V AC |
Voltage Range | 12 ~ 30V DC | ||
Alarm Current @24V DC 470Ω | 40mA | 40mA | 35mA |
Standby Current @24V DC 470Ω | under 100μA | ||
Sensor Type | Ultraviolet | ||
Sensitivity Angle | 120° | ||
Sensitivity Range | It can detect flame of 15mm at distance of 3m | ||
Ambient Temperature | -10℃ ~ +55℃ | ||
Material | Fire-proof plastic | ||
Dimensions | 111mm(Dia.) x 47mm(H) | ||
Weight | About 170g | ||
Color | White |